Can PUPI crossarms be field drilled, and where is it OK to drill holes?

Yes, field drilling is acceptable per the PUPI Usage and Installation Guidelines literature. Contact PUPI applications engineers if desired hole locations vary from what is described within the Usage and Installation Guidelines.

Can PUPI crossarms be mounted to flat poles with the standard mount?

Yes, crossarms fitted with standard mounts can be mounted to flat poles with the use of a flat pole adapter bracket. Alternate mounts designs with flat back plates are also available depending on the application.

What is the maximum angle we can turn on a tangent (or deadend) arm?

Maximum conductor angles are entirely application dependent. PUPI has the necessary test data to validate various line designs however, it is highly recommended that end user engineers contact PUPI applications engineers when specifying the appropriate crossarm series for their specific design needs.

What should we look for during routine maintenance and inspection of installed PUPI crossarms?

Routine maintenance procedures for PUPI crossarms are the same for fiberglass as they are for wood. Inspect for damage in high stress locations and around holes if the line has been subjected to an overload type event.

What type of protection do PUPI arms have against UV?

Our thermally bonded SunGUARD® UV coating has shown, in multiple climates, to resist weathering and fiber blooming which ultimately reduces the propensity for arc tracking. This externally applied coating is part of the three-layer UV protection system that gives PUPI crossarms a 60+ year service life.

How much tension can the guy plate on the mount support, and at what angle (single or double attachment)?

30,000 lbs at 30, 45, and 90 degrees.

Are there torque guidelines for installing PUPI crossarms?

Internal TorqueGUARD™ bushings, installed in every factory-drilled hole, prevent crush damage from overtightening. This feature can withstand over 450 ft-lbs of bolt-tightening torque.

What are advantages of the increased basic insulation level (BIL) that fiberglass crossarms provide?

Fiberglass is a non-conductive material and has insulating properties. Other manufactured crossarm materials like steel do are conductive and do not offer this benefit.

What is the service life of the PUPI crossarm assembly?

60 years.

Is there additional lead-time or cost associated with a custom drill pattern for a PUPI arm?

No, custom designs and drill patterns do not add to standard lead-times.

Can a PUPI deadend be mounted where we would be pulling the arm away from the pole?

No, this set up is not recommended because the system strength is then reliant on the fasteners instead of the crossarm and pole.

Does PUPI offer mounts with closed holes instead of open slots (when considering uplift)?

Yes, application specific mounts are available upon request.

PUPI crossarms are available in what colors?

Gray and Brown.

How is the PUPI Distribution pole constructed?

PUPI Distribution poles are single-piece, tapered poles made of fiberglass composite.   The composite formulation and lay-up was developed specifically for the application, leveraging our long-term technology expertise and in-field performance of PUPI crossarms and Alliance light poles.  Additionally, the UV resistance and longevity of the product is ensured by utilizing our SunGUARD® UV‑resistant coating. This base technology has been proven in the field for more than three decades as our PUPI crossarm coating technology. Additionally, broad spectrum UV inhibitor is formulated into the resin system itself to provide additional UV protection in the case of surface scratching or other superficial damage.

Do you require special hardware to be used on your poles?

The PUPI distribution pole was intentionally designed to allow standard, non-cleated utility hardware to be used. We completed a full range of application-specific testing to validate performance using common 3” curved washers; including torque, bearing, guying, and pull through.

How should we lift and handle PUPI poles during transportation?

SunGUARD® UV coating provides a durable surface for general handling and transportation. If mishandled, scratches to the surface coating may occur. Minor scratches in the protective coating are not cause for concern and do not affect pole performance.

Use of a large (6 ft. or larger) nylon lifting strap is recommended.

Do you have any recommendations for framing your poles during installation?

Generally, line crews have found it easiest to field drill and frame on the ground, before setting poles. PUPI® distribution poles can be field drilled using a carbide tip auger bit. Drilling from both sides of the pole will help keep the pole surface free of fibers and create a smooth surface for hardware connection points.

Do you have any no-drill zones on your poles for field drilling?

PUPI poles are single piece, and do not require assembling sections together prior to installation. Furthermore, as a single piece, our poles do not have no-drill zones like those required by segmented poles.

What are your hole spacing requirements for field drilling?

A minimum center to center distance of 3” is required for through bolts and any other drilling locations. This 3” distance is also required from the top of the pole. Chalk or marker can be used to mark drill locations on the pole. If you have a need for smaller spacing than 3” for a specific structure, reach out to PUPI Applications Engineering at pupisales@geotek.com to discuss.

When installing hardware on your poles, what is the torque requirement?

Hardware torque should not exceed 50 ft-lbs. In the field, this torque level is typically achieved by tightening the hardware until snug, then applying an additional ½ turn.

What happens if a bolted connection is over-torqued?

Excessively over torquing hardware can cause the pole to lose its circular cross section. If this is observed, simply loosening the bolt will allow the pole to return to its appropriate shape. Although known for their use on wood poles, reinforcement bolts offer different advantages when used with PUPI fiberglass poles. When installed perpendicular to load locations, reinforcement bolts can be used at high load locations to enable a more efficient use of the composite material’s strength and to maintain a circular cross-section.

If you have questions on the appropriate use of reinforcement bolts at guyed, or other high-load locations, reach out to PUPI Applications Engineering at pupisales@geotek.com.

What type of backfill can be used with your poles?

Set poles in native soil, free of sharp rocks. When backfilling poles with something other than native soil, use of gravel (3/4” or smaller) or pole foam is recommended. Recommended setting depth is 10% of total pole height, plus 2 feet.

How would you attach a ground wire?

Ground wires can be installed either inside or outside the pole:

Outside the pole: Use wire clips sized for their preferred ground wire, secured to the pole exterior with self-tapping screws.

Inside the pole: A common approach is to drill a hole below ground line to connect the ground wire to the grounding rod and drill another hole >10 feet above ground line to transition the wire outside the pole for equipment connection. The wire can be routed between these holes inside the pole using a fish tape or similar tool.

Can pole steps be used on your distribution poles?

Customers can install commercially available pole steps that are designed for use with FRP poles. PUPI poles can be factory drilled with holes for pole steps.

Is there a strength reduction factor that should be used when designing with a PUPI distribution pole?

PUPI recommends NESC load factors and strength factors be used to determine the appropriate design capacity for FRP structures, which are defined in NESC Tables 253-1 and 261-1.

As a result, PUPI does not prescribe a single equivalent reduction factor (such as 0.8–0.9) for fiberglass poles; instead, compliance with NESC criteria ensures appropriate long-term performance and safety.